Governor Model: WT4T
Following checks and corrections are applied during Validation and AutoCorrection.
- If dPmx < Pmnthen swap the values. If dPmx < 0 then dPmx change sign to positive. If Pmn> 0 then change sign to negative.
- If 0.0 < Tpw < 0.5*Mult*TimeStep then Tpw = 0, ElseIf 0.5*Mult*TimeStep < Tpw < Mult*TimeStep then Tpw = Mult*TimeStep
- If 0.0 < Tf < 0.5*Mult*TimeStep then Tf = 0, ElseIf 0.5*Mult*TimeStep < Tf < Mult*TimeStep then Tf = Mult*TimeStep
- If Kip > 1/(Mult*TimeStep) then Kip = 1/Mult*TimeStep
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
Model Equations and/or Block Diagrams
Parameters:
| MWCap | Turbine Rating, MW |
| Tpw | Pelec time constant, sec |
| Kpp | Pitch control proportional gain |
| Kip | Pitch control integral gain |
| Tf | Washout time constant, sec |
| Kf | Model Parameters\Kf |
| dPmx | Maximum PI limit, pu |
| dPmn | Minimum PI limit, pu |